Type 1 vs Type 2 SPD in Solar DCDB

Type 1 vs Type 2 SPD in Solar DCDB: Choosing the Right Surge Protection

A solar array is a large metal structure spread across an open roof or field, connected to sensitive electronics by long cables. That makes it very good at collecting surges, from direct lightning strikes, from strikes nearby, and from switching on the grid. The surge protective device (SPD) in the DCDB is what stands between those surges and the inverter. The most common question we get from EPC teams is whether a DCDB needs a Type 1 or a Type 2 SPD. The short answer: Type is not a quality grade. It describes what kind of surge current the device is designed to carry, and that depends on how the site is exposed to lightning. This guide explains how to choose.

What an SPD Does in a DCDB

An SPD is normally non-conducting. When a surge raises the voltage across it above a threshold, it conducts, diverting the surge current to earth and limiting the voltage the inverter sees. When the surge passes, it returns to its non-conducting state. An SPD does not replace a fuse, breaker, isolator, earthing system or external lightning protection system. It is one part of a coordinated protection scheme.

Type 1, Type 2 and Type 1+2 Explained

Feature Type 1 Type 2 Type 1+2
Designed for Partial direct lightning current Induced and switching surges Both, in one device
Test waveform 10/350 μs 8/20 μs Both
Key rating Iimp (impulse current) In (nominal) and Imax (maximum) discharge current Iimp and In
Typical location Where lightning current can enter the system Inverter input, combiner, DCDB Exposed sites needing both duties
Energy handling Very high Moderate High
The 10/350 μs waveform carries far more energy than the 8/20 μs waveform at the same peak current. So a 20kA Type 2 rating and a 12.5kA Type 1 rating are not comparable numbers. Compare ratings only under the same waveform.

When Is a Type 1 SPD Needed?

The deciding question is whether partial lightning current can flow into the DC system.
Site situation Typical SPD choice
Rooftop PV, no external lightning protection system (LPS) Type 2
Rooftop PV, external LPS present, separation distance maintained Type 2
Rooftop PV, external LPS present, separation distance cannot be maintained (array bonded to the LPS) Type 1 or Type 1+2 at the relevant entry points
Ground-mount or utility-scale plant in an exposed open area Project-specific study; often Type 1+2 at combiner or entry points, Type 2 at the inverter
Long DC cables between array and inverter SPDs at both ends may be needed
The separation distance is set by the lightning protection design under IEC 62305. If the PV structure is directly bonded to the air-termination system, part of a lightning strike can flow through the PV conductors, and that is Type 1 duty.

The Ratings That Actually Matter

Ucpv: the maximum continuous PV voltage

This is the most important rating, and the one most often chosen wrongly. Ucpv must be at or above the maximum string open-circuit voltage, calculated at the lowest site temperature. Module voltage rises on cold mornings. A string that is 900V at standard conditions can exceed 990V when cold. A 1,000V label is not an automatic match.

Up: the voltage protection level

Up is the voltage the SPD lets through during a surge. It must be lower than the impulse withstand voltage of the equipment it protects, usually the inverter’s DC input. Long connecting leads add voltage, so the installed protection level is higher than the marked Up.

In, Imax and Iimp

In is the current the SPD can discharge repeatedly. Imax is the maximum it can survive once. Iimp is the Type 1 lightning current rating. Choose these from the risk assessment, not from the biggest number on a catalogue page.

ISCPV: short-circuit current rating

A PV SPD must be able to handle the PV array’s short-circuit current if it fails, without catching fire. Its declared PV short-circuit rating must be at or above the array’s maximum short-circuit current at that point.

Relevant Standards

Standard What it covers
IEC 61643-31 Requirements and tests for SPDs on the DC side of PV installations, up to 1,500V DC
IEC 61643-32 Selection and application principles for SPDs in PV installations
IEC 62305 Lightning protection, including risk assessment and separation distance
IEC 60364-7-712 Electrical installation requirements for PV systems
Always specify a PV-rated DC SPD tested to IEC 61643-31. An AC SPD or a general DC SPD is not designed for the way PV current behaves under fault.

Where to Place SPDs in a Solar System

  • At the inverter DC input: almost always. If the inverter has a built-in SPD, check its rating and type.
  • At the DCDB or string combiner box: when the DC cable to the inverter is long. Many design guides use roughly 10m as a trigger to consider protection at both ends. Treat it as a design checkpoint, not a fixed rule.
  • On the AC side: an AC SPD in the ACDB protects against grid-side surges.
  • On data lines: RS485 or Ethernet monitoring lines also need protection on exposed sites.

Installation Details That Decide Performance

  • Keep leads short. Every extra length of conductor adds inductive voltage during a surge. Many guides recommend keeping the total lead length to the SPD under about 0.5m.
  • Use proper earthing. The SPD earth must connect to the equipotential bonding system with a low-impedance path.
  • Use the backup protection the SPD manufacturer specifies. Do not upsize it because a previous device operated.
  • Choose replaceable cartridges with a visual indicator. O&M teams can then replace a failed module without rewiring.
  • Use a remote signalling contact on larger plants. SPD failure then shows up on SCADA or a string monitoring box, not only during a site walk.

Common SPD Mistakes in Solar DCDBs

Mistake Risk
Ucpv chosen from nominal string voltage, not cold-weather Voc SPD conducts continuously and fails or catches fire
AC SPD used on the DC side No safe DC fault interruption
Type 2 used where lightning current can enter the system SPD destroyed by first nearby strike
Long, looped earth lead Inverter sees much higher voltage than the marked Up
No status monitoring Failed SPD goes unnoticed for months

Why Work With Synchro Electricals

Synchro Electricals designs solar ACDB DCDB boxes, string combiner boxes and the 1500VDC Solar DCDB Panel from your string data and site conditions. We select SPD type and ratings from your array voltage and lightning exposure, share drawings for approval before ordering components, and test every unit before dispatch with a test report supplied. Our quality system is ISO 9001:2015 certified (view certificates). For a full DCDB component list, see our solar DCDB component checklist (activate once live).

Conclusion

Choosing between a Type 1 and Type 2 SPD in a DCDB is a question about lightning exposure, not quality. Most rooftop systems without an external lightning protection system use Type 2. Systems where lightning current can reach the DC conductors need Type 1 or Type 1+2. In every case, Ucpv must cover the cold-weather string voltage, Up must sit below the inverter’s withstand level, and the leads must be short. Share your string configuration and site details with our team for a DCDB designed around the right surge protection. Contact us.

FAQs

1. What is the difference between a Type 1 and Type 2 SPD?

A Type 1 SPD handles partial direct lightning current, tested with a 10/350 μs waveform. A Type 2 SPD handles induced and switching surges, tested with an 8/20 μs waveform.

2. Which SPD is used in a solar DCDB?

Most rooftop DCDBs use a Type 2 PV-rated DC SPD. Where an external lightning protection system is bonded to the array, a Type 1 or Type 1+2 SPD is needed.

3. Do I need a Type 1 SPD for rooftop solar?

Only if partial lightning current can enter the PV system, usually when the array is bonded to an external lightning protection system and separation distance cannot be kept.

4. What does Ucpv mean on a DC SPD?

Ucpv is the maximum continuous voltage the SPD can withstand on a PV system. It must be at or above the maximum string open-circuit voltage at the lowest site temperature.

5. Can a 1000V SPD be used on a 1000V solar system?

Only if the string’s cold-weather open-circuit voltage stays within the SPD’s Ucpv. Check the calculation rather than the label.

6. Can I use an AC SPD on the DC side of a solar system?

No. Use a PV-rated DC SPD tested to IEC 61643-31, which is designed for the way PV current behaves under fault.

7. What is Up in an SPD?

Up is the voltage protection level, the voltage passed to the equipment during a surge. It must be below the inverter’s impulse withstand voltage.

8. Is a higher kA rating always better?

Not necessarily. A higher Imax can mean a longer life under repeated surges, but the right choice depends on Type, Ucpv and Up. Compare kA ratings only under the same waveform.

9. Do I need an SPD in both the DCDB and the inverter?

Often yes, when the DC cable is long. Many guides use about 10m of cable as a checkpoint to consider SPDs at both ends.

10. How long should an SPD earth wire be?

As short and straight as possible. Many guides recommend keeping the total lead length under about 0.5m, because each extra length adds voltage during a surge.

11. How do I know if an SPD has failed?

Most PV SPDs have a visual indicator window that changes colour on failure. Many also offer a remote signalling contact for monitoring systems.

12. Should a solar DCDB SPD be replaceable?

Plug-in cartridges are recommended, so failed modules can be replaced without rewiring or removing the base.

13. Does an SPD protect against a direct lightning strike?

An SPD is only one part of lightning protection. Direct-strike protection needs an external lightning protection system designed to IEC 62305, coordinated with the SPDs.

14. Which standard covers solar DC SPDs?

IEC 61643-31 covers PV DC SPD requirements and tests, and IEC 61643-32 covers selection and application.

15. What is a Type 1+2 SPD?

A combined device that meets both Type 1 and Type 2 tests. It handles partial lightning current and limits voltage to a level suitable for equipment.

16. Do monitoring cables need surge protection?

On exposed sites, yes. RS485 and Ethernet lines can carry surges into the inverter or data logger.

Need More Information?